1 Phase 2 Wire Multi-Rate KWH Meter - 5510D-T

Main functions
  • Good reliability
  • Small in volume, light in weight
  • Nice appearance
  • Easy installation
  • May select between 35mm DIN rail installation or installation on the board.
  • 3 tariffs, 12 daily periods of time, may select single tariff function in weekend.
  • Inner emplaced clock, in power cut situation, the message is preserved forever, inner emplaced spare batteries and free of maintenance.
  • The direction of electric power can be distinguished automatically, accident is checked automatically.
  • Infrared carrier wave communication and RS485 serial port communication, meter is set up by program and password is protected.
Model & Ordering

    

Specification
  • Nominal voltage (Un) : 230V AC
  • Operational voltage : 161 - 300V AC
  • Insulation capabilities :
    • AC voltage withstand : 2KV for 1 minute
    • Impulse voltage withstand : 6KV ¡V 1.2/50µS waveform
  • Available models : 1,5(6)A - 2,5(10)A - 3(12)A - 5(20)A - 5(30)A - 10(40)A - 10(60)A - 20(100)A
  • Operational current range :
    • 0.05Ib~Imax (Direct)
    • 0.02Ib~Imax (with CT)
  • Starting current range :
    • 0.004Ib (Direct)
    • 0.002Ib (with CT)
  • Over current withstand : 1200A for 0.5s
  • Operational frequency range : 50Hz + 10%
  • Internal power consumption : < 2W / 10VA
  • Test output flash rate : 800 impulses per kWh
  • Power supply indication :
    • Green indicator : Meter is connected and OK
    • Red indicator : Red led shows impulse rate
¡@