Home > Products > CP Series > CPPF

Power Factor Transducer CPPF

Model & Ordering

      

 

Input & output parameters

      

 

Specification
  • Accuracy ( 23 + 5 oC ) : 0.2% ro
  • Stability : Maximum 100ppm/oC, less 0.2% drift per year typically
  • Input burden : Current 0.3VA typically, voltage 0.2VA typically
  • Frequency : 50 + 2HZ, 60+ 2HZ
  • Maximum input over :
    • Current related input : 2 x rated continuous, 10 x rated 10 sec, 25 x rated 2 sec, 50 x rated 1 sec
    • Voltage related input : Voltage related input : maximum 2 x rated continuous ( 120V / 240V ), maximum 1.5 x rated continuous ( 415V )
  • Output load :
    • DC current mode : maximum 10V drop
    • DC voltage mode : maximum 5mA drive
  • Response & ripple < 400ms for step change 0-95%, ripple less 0.5% ro peak-peak
  • Magnetic effect < 0.05% change 1M center 100 amper-turn, synchronized with line frequency
  • Aux. power effect < 0.005% for per voltage change
  • Dielectric strength :
    • 4KV AC rms 1 minute between terminals to case IEC 688
    • 2KV AC rms 1 minute between input / output / power IEC 688
  • Impulse / SWC : IEC 255-4, 5KV 1.2x50us, IEC255-22-1, 2.5KV ( 1MHz / 400Hz )
  • Operating condition : -5 to 60oC, 20 to 99% RH non condensing
  • Storage condition : -20 to 70oC, 20 to 99% RH non condensing
  • Radio screening : RFI degree N complies with VDE 0875
  • Enclosure code : Case IP 50 / terminals IP 30, complies with IEC 529, BS 5490 DIN 40050
  • Power supply : AC 120V / 240V + 15%, 50 / 60Hz, < 7VA
¡@


Hsiang Cheng Electric Corp. (C)(P)2007 | Ver. 3.2 | Legal Notice | Feedback | Sitemap | Contact