Functions
DTU 2000 series is generally installed at on-site power stations to apply the monitor and control of signal
performance. DTU 2000 series is designed in multiple processor technique. Each I/O Card has its own processor
that is responsible for the basic data acquisition function. The basic functions are as follows.
- Data Acquisition Processing
DTU acquires digital and analog signal from station plus processing and storage in the memory and
ready to transmit the data back to communication server or control center.
- Sequence of Event Report
DTU provides the SOE function (Sequence of Event) to monitor the status and sequence, or any changes
of equipments at the station. An event is defined as a single change of state. Each time an event is
detected, RTU will time tag the event and save a description of the event and the time tag in a first in
first out (FIFO) butter. There is 1024 events butter in DTU.
- Control Output
Two types of control command can be transmitted from the Master Station to devices in the power
system via the DTU. One is Trip / Close command, the other is Direct Set point command.
There are two types of control output using Trip/Close command. One is ON / OFF operation
output to control CBs, ABSs and the other is Regulation operation output (raise / lower) to control
the position of transformer taps. Two types of Trip / Close commands are supported.
- Communication Function
The communication function of DTU can be divided into internal communication and external communication.
- SCADA Master: CDC Type II, DNP3.0, IEC870-5, CDT (China).
- DTU Sub-Master: ModBus RTU, DNP3.0, IEC870-5.
- IED : ModBus RTU, DNP3.0.
- Self-diagnostic Function
DTU is designed with self-diagnostic function. Every abnormal status of DTU is recorded as System Event, or
indicated by LED excitation on the panel. The System Event record can be retrieved by test set and store in its
hard disk, which is very easy to detect errors in maintenance.
- Programmable Algorithm Function
DTU has the capability of user definable "Sequential Algorithm". The "Sequential Algorithm" within DTU can
communicate through a common variable database which consists of analog inputs, digital inputs, accumula
tor inputs, pseudo points, alarm (system) status, digital output, and system clock.
Hardware Structure
DTU hardware structure is designed as a plug-in type set up in a 19" rack. The plug-in type configuration is ideal for maintenance
and expansion. The dimension of the card is followed by the European standard of 100mm * 160mm. DTU is consists of 4 Units.
- Power Supply Unit
The power supply of DTU contains the following cards :
- L-PS Card :
Power supply card comes in DC 18V - 40V Input and DC 5V (10W), DC 24V (3W) output; connects the back
plane with 48-pin DIN connector that supplies 5V working power for the DTU and 24V driving power for DOH card.
- H-PS Card :
Power supply card comes in AC 85V-265V or DC 65V - 375V input and DC 5V (10W), DC 24V (3W) output;
connects the backplane with 48-pin DIN that supplies 5V working power for the DTU and 24V driving power for DOH
Card.
- Main Unit
The main unit of DTU consists of 1 backplane and 1 Master CPU card.
- Backplane :
Backplane acts as buffer to the path of power supply and communication bus and with plugging slots for all
circuit cards. Backplane consists of one power slot, one CPU slot and several I/O slots. Backplane is designed as pluggable
type terminal for external wire connection.
- CPU Card :
Uses 16-bit high speed microprocessor, with one Ethernet LAN port (RC-717 only) or one isolated RS-232/485
ports for host communication, one RS-232/485 port for power meter or IEDs, one RS-485 port for local IO communication,
and one isolated RS232 port for Test Set.
- I / O Interface Unit
DTU provides various types of I/O interface cards, which corresponds to the system requirements in a station. I/O card is able
to devide into different functions of input and output which is to monitor and to study the status of operation in stations. The
detailed description is listed as below :
- DI Card :
Digital Input Card, 8 Points / Card. I/P : 8 channels at DC 24V, 48V, or 125V.
- ACC Card :
ACC Card : Accumulator Card, 8 Points / Card for 2-wire input; 4 Points / Card for 3-wire input.
I/P : 4 / 8 channels at DC : 24V, 48V, or 125V.
- DO Card :
Unlatch Digital Output Card, 8 Points / Card. O/P : 8 channels.
- DOH Card :
Unlatch Digital Output Card, 4 Points + 1. O/P : 4 channels with 1 Main Execution.
- ME (Main Execution) / Card.
- AI Card :
Analog Input Card, 4 Differential Channels / Card, 1 sec Scan Time.
I/P : +1mA, 4 channels; I/P : 4 - 20 mA, 4 channels; or I/P: 5V, 4 channels.
- AO Card :
Analog Output Card, 4 Different Channels / Card. I/P : +1mA, 4 channels; or I/P: 4 - 20 mA, 4 channels.
- Intelligent Power Meter module
The UP 6700 series Digital Power Meter is plug-in type and microprocessor based instrument which intends for power and
energy measurement. Additional functionality options are to provide control functions such as synchro check to undervoltage,
overvoltage, underfrequency, overfrequency and etc. The UP 6700 series is an Intelligent Electronic Device (IED) which
stores there measurements and setting parameters in internal registers for communication. With the features, high accuracy,
fully modularized & plug-in design, and compact size, UP 6700 series is very suitable module for Electric Utility Substation
Automation application.
¡@ |