The HC DTU 2200 series Distribution Terminal Unit are microprocessor-based units intended for small, medium or large data collection & supervisory control applications. The DTU 2200 is the Multi-Circuit LV Monitoring Module, which is adapted for monitoring of LV load current. It is required to provide a solution for load current monitoring for the LV distribution board.

 

Features
  • Multi-processor Technology & Distributed Architecture.
  • RTU mode Modbus or DNP3.0 (Level 2) compatible.
  • True RMS Conversion.
  • 24 sets AC Current input (eight 3-phase or six 3-phase LV circuit plus neutral current).
  • 3 sets AC Voltage input (1 * 3 phase).
  • Provide Programmable Setpoint Functions (over/under current, over/under voltage, over/under KVA, phase loss A/B/C, High Temperature Alarm Output).
  • Over 30 Power and Energy paraments (option).
  • 1 DC Analog Input (option).
  • Low input burden & high accuracy.
  • Wide power supply range.

 

Model & Ordering

 

Specification
  • Communication
    • RTU mode ModBus or DNP3.0 (Level 2) protocol
    • 1.2K to 19.2K baud, programmable parity
    • RS-485 * 1, 2/4 wire multi-drop, isolation
    • RS-232 * 1, 9600 baud, isolation
  • AC Current Input
    • 24 sets ac current input (eight 3-phase or six 3-phase LV circuit plus neutral current)
    • 32 samples per cycle, 16-bit resolution, input burden < 0.5VA
    • 1A or 5A nominal input range, 0.01 ~ 1.5 * CT conversion range, 0.5% fs accuracy
    • Pogrammable CT ratio
  • AC Voltage Input
    • 3 sets ac voltage input (1 * 3 phase)
    • 32 samples per cycle, 16-bit resolution, input burden < 0.05VA
    • 120V, 240V or 480V nominal input range, 0.05 ~ 1.2 * PT conversion range, 0.5% fs accuracy
    • 40 ~ 70Hz frequency i/p, + 0.02Hz accuracy
    • Programmable PT ratio
  • Analog Input (option)
    • 4 ~ 20mA (250), 0 ~ 10VDC (1M) normal input range, 150% overload
    • 1 sec scan time
    • 12-bit resolution, 0.25% accuracy @ 25oC, 50PPM/oC
    • 100dB CMRR @ 50/60Hz, 70dB NMRR @ 50/60Hz
  • Power Parameters Conversion (option)
    • Voltage, L-N Average & Individual
    • Power Factor total & Individual, 0.5% fs accuracy
    • W, Var, VA total & Individual, 1% accuracy
    • WH, VarH, VAH 1% accuracy
    • Frequency 0.1% accuracy
  • Power Supply
    • DC20V ~ DC60V input range (9.6W maximum)
    • AC85V ~ AC265V input range (9.6VA maximum)
  • Environmental
    • -25oC ~ 70oC operating temperature
    • 5% ~ 95% RH operating humidity
    • SWC Test :
      • ANSI/IEEE C37.90.1-2002 2.5KV Oscillatory & 4KV Fast Transient Test
      • IEC 61000-4-12 Class III & IEC 61000-4-4 Class IV Test
    • Impulse Test : IEC 61000-4-5 Class IV Test
    • Dielectric Strength : ANSI/IEEE C37.1-1979 / IEC 255-5 (2KV AC rms 1 minute)
    • ESD Test : IEC 61000-4-2 Class III Test
    • RFI Test : IEC 255-22-3 Class III Test (CE certify : EN50081-1 Class A, EN61000-3-2 Class A, EN50082-1)
    • SHOCK Test : IEC 255-21-2 Class I Test
    • Vibration Test : EN 50125-3
  • Dimension : 300mm (L) * 110mm (W) * 60mm (H)
¡@