Model & Ordering

Specification
- Input
- Range
- Voltage : 10 ~ 580V
- Current : Suitable for CT secondary rating (option)
- Maximum 6A for 5A rating
- Maximum 1.2A for 1A rating
- Frequency : 40 ~ 70Hz
- Burden
- Voltage < 0.5VA at 580V
- Current < 0.2VA at rating
- Overload rating
- Measured system
- Suitable for 3 phase 4 wires / 3 phase 3 wires
- Select by input wiring & software configuration
- Programmability
- Communication accessible / password lock (for communication)
- System selection : 3 phase 4 wires / 3 phase 3 wires
- PT : 1 - 5000.0 ; CT : 1-5000.0
- Readout display control 4 digits / auto scan
- Communication Baud rate 1200 / 2400 / 4800 / 9600 / 19200, Address setting 1 - 254
- Memory : all of energy date and status setting
- Communication port
- RS-485
- MODBUS(R) RTU protocol
- LCD 0.3" display, 1 rows of "8" digitals
- Dielectric strength
- IEC 255-5
- 2KV AC rms 1 minute between input / power
- Impulse and surge test
- ANSI / IEEE C37.90.1-1989 (3KV) SWC test
- IEC 255-22-1 class III SWC test
- IEC 255-22-4 class IV (IEC 801-4) SWC test
- IEC 255-5 1.2 * 50us (4KV) impulse test
- Stability
- Temperature range -10 to +55oC, maximum 100 ppm/oC
- Long term stability 0.15% drift maximum per year
- Operating condition : Temperature range -10 to +60oC, RH 20 ~ 95% non-condensed
- Storage condition : Temperature range -25 to +70oC, RH 20 - 95% non-condensed
- Power supply
- AC 80 ~ 260V, 40 ~ 70 Hz, DC 80 ~ 330V
- DC 20 ~ 60V
- Dissipation maximum 2 VA for AC and 1 Watts for DC
- Mounting / Dimension
- Panel type mounting
- Size : 118 * 98 * 48 mm
- Cut out : 92 * 44 mm

** For more detail information or software backup please contact Hsiang Cheng Electric Corp. or representative sales department.
¡@ |