Home > Products > GP Series > GPA/GPAS/GPAR

Digital Power Transducer for Utility GPA / GPAS / GPAR

Model & Ordering

      

 

Specification
  • Accuracy ( 23 + 5 oC ) : +0.3% RO according to IEC688-1, +0.5% GPAR
  • Stability : 100ppm/oC, < + 0.2% drift per year, non cumulative
  • Input burden :
    • 0.3VA / element
    • 1VA / element (for GPAS)
  • Frequency : 50 or 60Hz, + 2HZ
  • Output load :
    • Current - 10V drop max.
    • Voltage - 5mA drive max.
  • Response time < 400ms for step change 0-95%
  • Magnetic effect < 0.05% change 1M centre 100 AT, synchronized with line frequency
  • Aux. power effect < 0.005% for per voltage change
  • Impulse test : 5KV, 1.2*50us, according to IEC 255-4
  • SWC test : 2.5kv, 1MHz according to IEC 255-22-1
  • Working condition : -5 to 60oC, 20 to 99% RH non condensing
  • Storage condition : -20 to 70oC, 20 to 99% RH non condensing
  • Radio screening : RFI degree N complies with VDE 0875
  • Enclosure code :
    • IP 50 (case)
    • IP 30 (terminal)
    • According to IEC 529 / DIN40050
  • Power supply :
    • Standard range : 110V or 220V + 15%, 50 / 60Hz, < 3.5VA ( for GPA & GPAR); < 8VA ( for GPAX)
    • Options : self power and other AC power supplies up to 440V AC on request. DC powered models available at additional costs
¡@


Hsiang Cheng Electric Corp. (C)(P)2007 | Ver. 3.2 | Legal Notice | Feedback | Sitemap | Contact