Features
- True process dc rate monitor
- Wide standard dc voltage & current input
- Rangable of idsplay scale for engineering unit
- High accuracy of 0.05%
- Option of dc linearty output or 24Vdc power output
- Two wire application
- 3-3/4 digits of maximum 3999 counts
- Display with super rate LED
Model & Ordering

Specification
- Accruacy (23 + 3oC) : 0.05% fs + 1 count
- Stability : Temperature coefficient < 50 ppm per degree C, long term draft < 0.1% per year
- Display & resolution : 0.56" super rate LED, 3-3/4 digits of maximum 3999 counts
- Response time : Sample rate 1 sec typically
- Input resistance > 1 M
for voltage input, < 20 for current input
- Input over : Maximum 1 ampere for current input, maximum 250V for voltage input
- Noise rejection : Cmrr > 120 db, Nmrr > 100 db.
- Operating condition : Temperature range -10 to 55oC, 0-99% RH non-condensed, storage -25 to 70oC
- Auxiliary power : AC + 15% < 3.5 VA, DC + 20% < 5 watts
¡@ |