Home > Products > PP1 Series > PP1V/PP1VR

Digital Power Transducer for Utility PP1V / PP1VR

Model & Ordering

      

 

Specification
  • Accuracy ( 23 + 5 oC ) :
    • 0.2% RO ........ PP1A, PP1AX, PP1V, PP1VX
    • 0.3% RO ........ PP1AR, PP1ARX, PP1VR, PP1VRX
  • Maximum output load : Maximum 10V drive for current output mode, maximum 5mA for voltage output mode
  • Dielectric strength :
    • 4KV AC rms 1 minute between terminals to case IEC 688
    • 2KV AC rms 1 minute between input / output / power IEC 688
  • Impulse test : ANSI C37.90 / 1989, IEC 255-3 5KV ( 1.2 * 50 us ), 3KA ( 8 * 20 us ) ..... current only
  • Surge test (ring wave) : ANSI C37.90 / 1989 ( 3KV~0.5us / 100KHz ), IEC 255-3 ( 2.5KV~0.25ms / 1MHz )
  • Maximum input over :
  •       
  • Input burden :
    • Current / less 0.2VA, voltage / less 0.25VA per element
    • 1VA per element ........ self power for V & A
  • Power effect : Less 0.003% for per volt change
  • Response time & ripple : Less 400ms typically, ripple less 0.5% ro peak to peak
  • Frequency : 48 to 65 Hz
  • Waveform : Sinusoidal
  • Stability : Temperature range ( -10 to +60oC ), long term stability / year
    • Maximum 100 ppm per degree C , less 0.1% drift
  • Storage condition : Temperature range -25 to +70oC, RH 20 to 95% non condensed
  • Operating condition : Temperature range -20 to +65oC, RH 20 to 95% non condensed
  • Magnetic field effect : Less 0.02% under 100 ampere -turns, at 1M center
  • Power dissipation : Maximum 3.5VA for PP1A / PP1AR / PP1V / PP1VR; 8VA for PP1AX / PP1ARX / PP1VX / PP1VRX
  • Dimension : W*H*D : 12T (60.6mm) * 3U (128.5mm) * 238mm
¡@


Hsiang Cheng Electric Corp. (C)(P)2007 | Ver. 3.2 | Legal Notice | Feedback | Sitemap | Contact