Features
- Multi-turns Potentiometer setting
- Dual Hi & Lo setting
- Wide input parameters & ranges
- Output with adjustable time delayer
- 4 digits up to 9999 counts
Model & Ordering

Specification
- Accuracy :
- 0.1% fs+ 2 counts for DC related input
- 0.25% fs+ 2 counts for AC related input
- 0.25% fs+ 0.5oC for temperature related input (cjc. error included)
- 0.25% fs + 1 counts for frequency related input
- Stability :
- Temperatue < 100 pm per oC, 5-50oC
- Long term stability < 0.15% draft per year
- Input burden :
- > 1 Megaohms for DC or AC voltage input sensing
- < 500 mV drop for DC current input
- < 0.5 VA for AC current sensing
- Display : 4 digits maximum 9999 counts, 0.56" super rate LED
- Setting :
- Hi & Lo set standard, Hi-Hi set optional
- Hi comparator setting < meter input output relay energied
- Lo comparator setting > meter input output relay energied
- Multi-turns potentiometer for each setting
- Switchable display range for S1, S2 & M (input measured)
- Response time :
- Analog conversion < 1 sec of average integration typically
- Analog to Digital conversion 2 sample rate per second
- Input over capability:
- Voltage maximum for 100V rms or 2 x full input which ever great current input
- DC version 2 times continuous, 10 times 2 sec., 25 times 0.5 sec.
- AC version 3 times continuous, 10 times 30 seconds, 25 times 2 seconds
- Frequency :
- 40-400 Hz AC related meters
- Specified range for frequency related meters
- Control output :
- On-off control type
- Relay contact output of spdt type for each setting
- Capacity AC250V / 2A, AC125V / 3A, DC24V / 3A
- Time delayer adjustable 0-30 sec. typically, 0-60, 0-120 sec. for option
- Dead band for option alternatively & availably to time delayer
- Output indication : LED lamp energied in front panel
- Comm. mode voltage : 2KV rms 50 / 60 Hz 1 minute
- Impulse voltage : 4KV 1.2 * 50 us common mode test
- Operating condition : 0 to 50oC, 20-90% RH non-condensed
- Storage condition : -10 to 70oC
- Power supply :
- Standard AC 110 / 220V 50 / 60HZ +15%, <5VA
- Option DC 12V / 24V / 48V / 125V, < 6 Watts
¡@ |