Features
- Programmable for PT & CT ratio
- True power system design compliant : ANSI-IEEE, IEC & VED standards
- High over capability
- 7 digits counter
- High accuracy of 0.2%
- Distorted waveform signal measurement
- Display with super rate LED
Applied rules & standards
- Measuring and conversion : IEC 60687
- Dielectric strength : IEC 60255-5
- Impulse / surge test :
- ANSI / IEEE
- C37.90.1-1989 (3KV) SWC
- IEC 61000-4-12 classIII SWC
- IEC 61000-4-4 classIV SWC
- IEC 61000-4-5 classIV Impulse
- Adaptability power system : IEC 0110
- Measuring reliability : VDE 3540
Model & Order Number

Specification
- Accuracy (23 + 3oC) : 0.2% rd / PF (PF = coscØ for WH version¡FPF = sinØ for VarH version)
- Output pulse :
- Photo couple isolator, open collector 300V
- 150mA maximum for 1 / 10 / 100 pulse / unit
- Ratio setting :
- PT ratio, range 1.0 - 5000.0
- CT ratio, range 1.0 - 5000.0
- Stability :
- Temperature range -10 to +50oC, maximum 70ppm/oC
- Digits & counts : Seven (7) digits 9999999 counts maximum
- Response time : Conversional rate less 1 sec typically
- Input burden : 0.2VA maximum per input element
- Input over :
- Current input : 2 * rating continuous, 25 * rating - 2 sec, 50 * rating - 1 sec
- Voltage input : 1.5 * rating continuous
- Dielectric strength :
- 2.5KVrms / 1 minute, all terminals to FG
- 2KVrms / 1 minute, between input / output / power
- Impulse and surge :
- ANSI/IEEE C37.90.1 - 1989 (3KV) SWC
- IEC 61000-4-12 classIII SWC
- IEC 61000-4-4 classIV SWC
- IEC 61000-4-5 classIV Impulse
- Operating condition :
- Operating temperature range -25 to 60oC, RH 0 to 95% non-condensing
- Storage temperature range -40 to 80oC, RH 0 to 95% non-condensing
- Power supply :
- Lo : DC 20 - 60V
- Hi : AC 80-260V @40 - 70Hz, DC 80 - 330V, Dissipation maximum : 10 VA for AC and 5 Watt for DC
¡@ |