Name: Multifunctional Power Quality Meter
Description: 
Overview

The UP 6760 Digital Power Meter is microprocessor-based instrument intended for power and energy measurement. Additional functionality options provide control functions such as synchro check. The UP 6760 is an Intelligent Electronic Device (IED) and stores these measured values and setting parameters in internal registers for communication. Featuring high accuracy, fully modularized & plug-in design, and compact size, the UP 6760 is very suitable for Electric Utility Substation Automation applications.
 

 

Features

  • Current input terminal with automatic shorting mechanism
  • Over 90 power and energy parameters for easy and quick access to information
  • Modbus(R) RTU / DNP3.0 protocol
  • 4-AC current inputs, 5A or 1A (specified upon ordering)
  • 4-AC voltage inputs, maximum 300V
  • True RMS conversion
  • 32 sample points per cycle
  • Instant maximum and minimum logger
  • Waveform capture
  • Error message display
  • 200 event logs for all measured quantities
  • Build in RTC (real time clock)
  • Field programmable PT / CT ratio
  • Accuracy up to 0.15%
  • Low input burden 0.5VA (5A / 120V)
  • 2 communication Port, RS-485 + RS-232
  • Wide power supply range 80~260V AC / DC
  • Memory for all setup and energy data
  • Comprehensive self test diagnostic
  • "User Map" speed up communication (indirect access to data)
  • Synchrocheck
  • Fault current detection .....optional
  • 2KV RMS input / output / power isolation
  • Alphanumeric LED display clear and long-life
  • Fully modularized & plug-in type
  • Easy in field maintenance


Model & Ordering

Specifications

Programmable measurements / Accuracy / Display readouts

       

Input

  • 4 - AC Currents ( Aa, Ab, Ac, A0)
  • 4 - AC Voltage (Pa, Pb, Pc, Pn for 3-phase input & P1, P2 for separate 1-phase input)
  • Range :
    • Voltage : 10~300V
    • Current : Switch able for CT secondary rating
      • Maximum 6A for 5A rating
      • Maximum 1.2A for 1A rating
    • AFx=20CT (Fault current) .....optional
    • Frequency 40-70Hz

Burden

  • Voltage < 0.15VA at 300V (or > 1 M)
  • Current < 0.2VA of rating     * Overload Withstand: 2 CT continuous, 25 CT 2 sec, 50 CT 1 sec

Display

  • LED / 0.2" / green color, 1 rows of 8 characters

Programmability

  • Communication Baud Rate
    • 1.2K / 2.4K / 4.8K / 9.6K / 19.2K bps, Device addresses 1 ~ 254
  • Measured Power System
  • 3P4W / 3P3W / 1P3W / 1P2W, 50 / 60 Hz main frequency
  • PT ratio 1.0~5000.0
  • CT ratio 1.0~5000.0
  • Maximum demand 1-60 minute (A, KW, KVAR, KVA)

Fault Current Detection (Mode 0) ..... optional

  • One Fault-Based-Curve
  • 16 set-point groups (Ip-pu, Mp, Ig-pu, Mg)

Fault Current Detection (Mode 1) ..... optional

  • User definable
  • 4-point Phase time over-current curve
  • 4-point Ground time over-current curve

 Waveform Capture

  • Data Channel : 4 currents, 4 voltages
  • Sample Rate : 32 points per cycle, length 2 cycle

 Maximum / Minimum Logger

  • 20 parameters with time-stamp: includes VP1, VP2, VP3, VPE, VPS, VL1, VL2, VL3, VLE, VLS, A1, A2, A3, A0, AE, W, Var, VA, PF, F

 Communication Port

  • RS232 (front panel) : Modbus RTU protocol only
  • RS485 (rear panel) : Modbus RTU or DNP3.0 protocol

 Real Time Clock (RTC)

  • Maximum deviation 2 sec in 24 hours
  • Time for Year / Month / Day / Hour / Minute / Second

 Dielectric Strength

  • IEC 255-5
  • 2KV AC rms 1 minute between input / output / power
  • 2.5KV AC rms 1 minute between case / input
  • 2KV AC rms 1 minute between case / power

Impulse and Surge

  • ANSI / IEEE C37.90.1-1989 (3KV) SWC
  • IEC 61000-4-12 CLASS III SWC
  • IEC 61000-4-4 CLASS IV SWC
  • IEC 61000-4-5 CLASS IV Impulse

Stability

  • Temperature range (-10 to +50oC), maximum 100 ppm/oC

Operating Condition

  • Temperature range -25 to 60oC, RH 10 to 95% non-condensing

Storage Condition

  • Temperature range -40 to 80oC, RH 10 to 95% non-condensing

Event logger

  • 200 events with time-stamp
  • status change of switch input
  • Failure in self-test
  • Programming access
  • Fault current recorder .....optional
  • Power ON / OFF

Power Supply

  • LO : DC 20~60V
  • HI : AC 80~260V @ 40~70 Hz, DC 80~330 V
  • Dissipation maximum 12 VA for AC and 5W for DC

Dimension

  • 208 * 72.6 * 144.6 mm (L * W * H)