Power Transducer

SPVX-Metal Case

HC power voltage transducer is with reading base accuracy conversion ideally applied for an accurate
measurement of AC voltage input, with self power mode of non external power design to simplify wire
connection particularly useful for user in field application
Models are available for three voltage units with average responding scaled to RMS output..
  • Self - power mode
  • Standard output with 0 to 1 mAdc
  • Accuracy of reading base 0.25% reading + 0.02% ro
  • Rugged steel enclosure of high magnetic immunity
  • Meets IEEE SWC test
  • Accuracy : 0.25% RD + 0.02%RO / 23 ± 3 °C
  • Input ( each element ) :
    • Range : Effective voltage 0 - 165V ; nominal voltage 120V
    • Over capability : 200V continuous 250V ... 10sec / hour; 300V ... 5sec / hour
    • Burden : Voltage < 3VA at 120V input
    • Frequency : 50 - 70Hz
    • Protection : Full protection for SURGE, EMI & RFI
  • Output ( isolated with input ) :
    • Range :
      • Standard DC 0 to + 1mA
      • DC 0 to +1mA calibration vs 0 to 150V
    • Output load : Maximum 10Kohm for 0 to 1 mA output
    • Output impedance > 30 Mega ohm
    • Response time < 400 ms from 0 to 99% RO at operating
    • Ripple < 0.5% P-P RO
    • Long term stability < 0.1% RO per year ( typically )
    • Temperature stability < 0.01% per degree C, from 0 to 55°C
    • Adjustment : Span ±5% / 10% on request ; zero ... none
    • Protection : No damage ... open or short; full protection for SURGE, EMI, & RFI
    • Magnetic effect < 0.04% at center 400 A-T / M
  • Operation condition
    • Temperature Environment : -5 ~ 60 °C
    • Humidity : 20~99% RH non condensed
    • Elevation : Under 3000 meters
    • Magnetic Field : 500 A-T / M
    • Waveform : Sinusoidal
    • Dielectric strength : 4KV AC rms 1 minute between input / output / power / case; fulfills IEC688 standards
    • Impulse Test: ANSI C37.90 / 1989, IEEE 587 / 1983, IEC255-3, 6KV (1.2 * 50 us), 3KA (8 * 20 us) ..... current only
    • Surge Test (ring wave) : IEEE 587 / 1983 (3KV - 0.5 us / 100 KHz), IEC255-3 (2.5KV - 0.25ms / 1MHz)
TOP