Multifunction Power Quality Meter

HC6030

The power quality meter HC 6030 is an ideal device to power monitoring in power quality when continuous monitoring to a power system is required.
The HC 6030 provides metering for current, voltage, real and reactive power, power energy, power factor, frequency energy demand and 8 TOU channels with tariff to power energy. 24 programmable setpoints and 3 assignable output relays allow control functions to be added for specific applications. This includes basic alarm on over / under current or voltage, unbalance, demand based load shedding, and capacitor power factor correction control. More complex control is possible using the 8 switch inputs which also can be used for status such as breaker open / closed, or pulse counter to flow information or demand synchronized trigger and etc.

The provided measurement to main of AC power and auxiliary of 3 analog process inputs, 8 digital inputs, the HC 6030 may be used as a data gathering device for a plant automation system that integrates process, instrument and electrical requirements.
The quality of the power system is important with increasing use of electronic loads such as switching power or variable frequency drives. With the HC 6030 auxiliary input / output, any phase current / voltage can be displayed and the harmonic content calculated. By knowing the harmonic distribution, action can be taken to prevent overheated transformer, motors, capacitors, neutral wires and nuisance breaker trips. Redistribution of system loading can also be determined. Waveform and chart recorder printouts available from the HC 6030 assist in problem diagnosis.

Ideal device to power monitoring in power quality system; with 8 TOU channels and tariff to power energy. 24 programmable setpoints and 3 assignable output relays allow control functions to be added for specific applications. More complex control is possible using the 8 switch inputs, and waveform and chart recorder printouts assists in problem diagnosis and etc.

Features

  • Medium and low voltage systems 
  • Commercial, industrial, utility 
  • Flexible control for demand load shedding, power factor, etc. 
  • Power quality analysis. 
  • A / W / Var / VA demand 
  • 8 digital inputs / pulse input totalizing 
  • 3 controlled relay outputs 
  • 3 analog process inputs 
  • 4 isolated analog outputs to a transducer function 
  • 2 pulse outputs based on KWH, KVarH, KVAH or AH 
  • 8 channels for time of use to power energy " "Metering of distribution feeders, transformers, generators, capacitor bands and motors 
  • Load shedding 
  • Power factor control 
  • Event log 
  • Minimum / maximum logger 
  • Data trend logger 
  • Waveform capture / harmonic analysis through 31rd 
  • Triggered trace memory ( Fault recording ) 
  • Ports : RS232 front, RS485 rear 
  • ModBus® RTU protocol " 

Accuracy

  • 0.15%fs for V x 3
  • 0.15%fs for A x 3
  • 0.25%fs for Watts
  • 0.25%fs for Vars
  • 0.25%fs for VA
  • 0.25%fs** for PF
  • 0.8%rd** for WH
  • 1%rd** for VarH
  • 0.15%fs for IO(AO)
  • 0.03%rd for Hz
  • 0.25%fs for Watt demand
  • 0.15%fs for Amper demand
  • 0.5%fs for DC Analog Input
  • Harmonic: 31th 
  • ** Accuracy performance range for WH/VarH/PF, Cosθ : 1-0.5 for WH/PF, Sinθ : 1-0.5 for VarH, Voltage≧50V, Current≧10% of rating

Certifications

  • CE
TOP