The model UMAF series are designed under micro base, and it also specially designed to solve the complicated ratio problem in CT variables, directly accept a secondary signals from CT & scale to a primary reading display.
The designed specifications of the units, truly a real power system design, compliant ANSI-IEEE & IEC, VDE .Those standards providing full protection for surge intrusion & unusual over input to assure reliable operation.
The designed specifications of the units, truly a real power system design, compliant ANSI-IEEE & IEC, VDE .Those standards providing full protection for surge intrusion & unusual over input to assure reliable operation.
- True power system design complaints ANSI-IEEE, IEC & VDE standards
- High over capability to assure reliable operation
- Ration programmable with field re-range ability
- High accuracy of 0.2% fs
- 4-1/2 digits maximum of 19999 counts
- Super rate display of 0.56"
- Accuracy (23 + 3℃) : 0.2% fs
- Stability : Temperature coefficient < 50 ppm per degree C. Long term draft < 0.2% per year
- Digits / counts / display : Maximum 19999 counts of 4-1/2 digits. 0.56" super rate LED
- Configuration : CT Ratio settable
- Response time : Sample rate 1 of per sec typically
- Input burden : 0.25VA maximum
- Input over : Current input : 3 x rating-continuous, 10 x rating - 30 sec, 25 x rating - 3 sec
- Frequency : 48 - 400 Hz
- Dielectric strength :
- 2.5kV rms / 1 minute, all terminals to reference ground (case)
- 2kV rms / 1 minute, input terminals to power terminals
- Surge test : ANSI C37.90.1 / 1989, IEC 255-3 (1989)
- Impulse test :
- Impulse voltage : 1.2 x 50 us 4kV
- Oscillation wave : 0.5us – 100kHz 3kV & 1MHz - 0.25ms 2.5kV
- Temperature condition :
- Operation -10 to 55℃, 0 to 99% RH non-condensed
- Storage -25 to 70℃, 20-99% RH non-condensed
- Auxiliary power : AC / DC version < 3.5VA, DC option version ±20% < 5 watts