HC PP/UPP series transmitters are a family of plugging unit type, set in a standard DIN 19" rack mounting or in an independent unit-enclosure which according to user application. Each plugging unit is designed & divided into two parts : input terminal module & converting module.
UPPTR-2 is the plug-in type RTD Isolating transducer with two outputs.
Measuring and conversion of IEC 688 . The adaptability for power system of VDE 0110, and Measuring reliability of VDE 3540.
*The PP series is a traditional analog product, and the UPP series is a new digital product. PP series products are partly replaced by UPP series, the input and output terminals and functions are the same, and can be directly replaced.
UPPTR-2 is the plug-in type RTD Isolating transducer with two outputs.
Measuring and conversion of IEC 688 . The adaptability for power system of VDE 0110, and Measuring reliability of VDE 3540.
*The PP series is a traditional analog product, and the UPP series is a new digital product. PP series products are partly replaced by UPP series, the input and output terminals and functions are the same, and can be directly replaced.
- Linear output
- Field - switchable input & output ranges
- Changeable input range modules
- Accuracy 0.3%
- High dielectric strength 4KV AC rms input / output / power / case
- Available standard or custom calibration
- Accuracy ( 23 ± 5 ℃ ) : 0.3% RO
- Linearity & repeatability : 0.1% typical
- Temperature stability : Less 0.015% ro per degree C
- Configuration :
- Three wires connection / applicable for two wire connection
- Excitation - 5mAdc constant current source
- Selectable input module
- Linear output vs input temperature
- Field rangeability :
- Selectable output mode for voltage or current mode
- Switchable of input ranges & output ranges
- Switchable AC power for 110V or 220V
- Selectable C / F calibration
- Effect of wire resistance :
- Automatically eliminated for 3 wire connections
- Offset recalibration required for 2 wire connections
- Input break detection :
- Selectable Hi-set or Lo-set
- Hi-set over 110% of rated output
- Lo-set less than 0.5% of rated output
- Power effect : Less than 0.003% per volt change
- Output drive capability : Maximum 10mA for voltage mode, maximum 10V for current mode
- Response time & ripple : Less 400ms typically, ripple less 0.15% rms of span
- Common mode rejection : > 80db 50 / 60Hz
- Dielectric strength : 4KV AC between input / output / power / case
- Impulse & surge test : IEEE 587 / 1983 or IEC 255-4
- Storage condition: Temperature range -25 to +70℃, RH 20 to 95% non condensed
- Operating condition: Temperature range -20 to +65℃, RH 20 to 95% non condensed
- Power supply:
- LO : DC 24 - 60V ± 20%
- HI : AC 80 - 260V @40 - 70Hz / DC 80 - 330V
- Dissipation Max. 12VA for AC / 10W for DC
- Dimension : WxHxD: 12T (60.6mm) x 3U (128.5mm) x 238mm