HC PP/UPP series transmitters are a family of plugging unit type, set in a standard DIN 19" rack mounting or in an independent unit-enclosure which according to user application. Each plugging unit is designed & divided into two parts : input terminal module & converting module.
UPPR-2 is the plug-in type Resistance Isolating transducer with two outputs.
Measuring and conversion of IEC 688 . The adaptability for power system of VDE 0110, and Measuring reliability of VDE 3540.
*The PP series is a traditional analog product, and the UPP series is a new digital product. PP series products are partly replaced by UPP series, the input and output terminals and functions are the same, and can be directly replaced.
UPPR-2 is the plug-in type Resistance Isolating transducer with two outputs.
Measuring and conversion of IEC 688 . The adaptability for power system of VDE 0110, and Measuring reliability of VDE 3540.
*The PP series is a traditional analog product, and the UPP series is a new digital product. PP series products are partly replaced by UPP series, the input and output terminals and functions are the same, and can be directly replaced.
- Tap changer & position application
- Field - rangeability : switchable input & output ranges
- Accuracy 0.2%
- High dielectric strength 4KV AC rms input / output / power / case
- Available standard or custom calibration
- Accuracy (23 ± 5 ℃) : 0.2% RO
- Linearity & repeatability : 0.1% typical
- Temperature stability : Maximum 0.008% ro per degree C
- Configuration:
- Two or three wires connection
- Excitation 5 / 0.5mAdc constant current source
- Field variety:
- Selectable output mode for voltage or current mode
- Switchable of input ranges & output ranges
- Switchable AC power for 110V or 220V
- Effect of wire resistance:
- Automatically eliminated for 3 wire connection
- Offset recalibration required for 2 wire connection
- Input break detection : Hi-set > 110% of rated output
- Power effect : Less than 0.003% per volt change
- Output drive capability : Maximum 10mA for voltage mode, maximum 10V for current mode
- Response time & ripple : Less than 400ms typically, ripple less than 0.1% rms of span
- Common mode rejection : > 80db 50 / 60Hz
- Dielectric strength : 3.5KV rms AC between input / output / power / case
- Impulse & surge test : IEEE 587 / 1983 5KV
- Storage condition : Temperature range -25 to +70℃, RH 20 to 95% non condensed
- Operating condition : Temperature range -20 to +65℃, RH 20 to 95% non condensed
- Power supply :
- LO : DC 24 - 60V ± 20%
- HI : AC 80 - 260V @40 - 70Hz / DC 80 - 330V
- Dissipation Max. 12VA for AC / 10W for DC
- Dimension : WxHxD : 12T (60.6mm) x 3U (128.5mm) x 238mm